Uninterruptible Power Supply
UPS2N Redundancy
A redundancy model in which every system component is fully duplicated, allowing one complete half to fail with no impact on the load.
Full Definition
2N redundancy means there are two complete, independent systems, each capable of carrying 100% of the critical load. In a 2N power configuration, a data centre would have two independent UPS systems (A-side and B-side), each fed from a separate transformer and generator, with dual-corded IT equipment connected to both. The failure of an entire A-side has no impact on the B-side.
2N is the architecture required for Uptime Institute Tier IV certification and is common in Tier III facilities. It is significantly more expensive than N+1 — capital cost roughly doubles for each redundant system — and typically results in equipment running at 40–50% utilisation, which reduces efficiency (UPS are most efficient at 75–100% load). 2N+1 adds a further spare component on top of the full redundant pair, providing concurrently maintainable fault tolerance with an additional safety margin.
Also Known As
Source Reference
Uptime Institute Tier Standard: Topology