Uninterruptible Power Supply
UPS2N Redundancy
A redundancy model in which every system component is fully duplicated, allowing one complete half to fail with no impact on the load.
Full Definition
<p>2N redundancy means there are two complete, independent systems, each capable of carrying 100% of the critical load. In a 2N power configuration, a data centre would have two independent UPS systems (A-side and B-side), each fed from a separate transformer and generator, with dual-corded IT equipment connected to both. The failure of an entire A-side has no impact on the B-side.</p><p>2N is the architecture required for Uptime Institute Tier IV certification and is common in Tier III facilities. It is significantly more expensive than N+1 — capital cost roughly doubles for each redundant system — and typically results in equipment running at 40–50% utilisation, which reduces efficiency (UPS are most efficient at 75–100% load). 2N+1 adds a further spare component on top of the full redundant pair, providing concurrently maintainable fault tolerance with an additional safety margin.</p>
Also Known As
Source Reference
Uptime Institute Tier Standard: Topology